Sensors and instrumentation#

A test stand measures with sensors and acts with actuators. Each one is either wired to a DAQ as a bare signal, or built into an instrument that exchanges messages with the computer.

Two ways in: wired to a DAQ, or through an instrument#

A transducer turns one physical quantity into an electrical signal, and nothing more. It’s wired to an input on a data acquisition (DAQ) system, which measures the signal. A fluids panel, which runs compressed air through valves, works this way: its pressure transducers, its switches and its valves are each wired to the panel’s DAQ.

An instrument has its own transducers, electronics and actuators built in. The computer exchanges messages with it over a communications bus instead of measuring its signals. An e-axle dyno, where a motor drives the e-axle under test and a load motor on each side brakes it, works this way: its motor controllers and its power supply are instruments.

Wired to a DAQ

Instrument

What crosses the wire

An electrical signal, such as a current or a voltage

Messages, such as “set speed to 1,000 RPM” or “speed is 998 RPM”

Where the measuring happens

In the DAQ

Inside the instrument

What you configure

The DAQ channel’s range, scaling and sample rate

The instrument’s settings, through its messages or its front panel

Example

A fluids panel

An e-axle dyno

A flow meter, for example, can come either way: as a bare transducer for a DAQ, or as an instrument with its own display and bus connection.

DAQ inputs and outputs#

A DAQ has four kinds of I/O point. The fluids panel’s DAQ uses a separate NI C Series module for each kind:

Kind

What connects to it

Example on the fluids panel

Module

Analog input

A sensor that reports a value in a range

p_1, the supply pressure

NI-9203, current input

Digital input

A sensor that reports on or off

sw_1, the slide’s retracted switch

NI-9421, 24 V digital input

Analog output

An actuator you set anywhere in a range

v_2, the proportional valve

NI-9265, current output

Digital output

An actuator you turn on or off

pump_1, the compressor’s relay

NI-9476, 24 V digital output

Analog signals come in several forms, and each needs a matching input: a voltage, a 4–20 mA current, a small voltage from a thermocouple, or a resistance bridge that needs power from the DAQ.

4–20 mA current loops#

A current loop carries a measurement as a current between 4 and 20 mA. A loop power supply, the transducer and the DAQ’s input are wired in series, in one loop.[1]

Current loops suit test stands and industrial sites for two reasons:[1]

  • The same current flows everywhere in a loop, so the wire’s resistance doesn’t change the reading the way it changes a voltage over a long cable.

  • The range starts at 4 mA, a live zero. A reading of 0 mA means the loop is broken, not that the value is zero.

A two-wire transducer takes its power from the loop itself. The WIKA A-10 pressure transducer, for example, runs from an 8–30 V supply and draws no more than 25 mA, its signal current.[2]

To scale a 4–20 mA reading to a value, use the transducer’s range:

value = low + (current − 4 mA) ÷ 16 mA × (high − low)

For p_1, a 0–100 psig transducer, 12 mA is 50 psig, and 17.6 mA is 85 psig.

Outputs can use the same signal. The fluids panel commands its proportional valve, v_2, with a 4–20 mA output.

Sensors by quantity#

Pressure#

A pressure transducer reports pressure relative to a reference. Gauge pressure, in psig, is relative to the surrounding air, so an open line reads 0. Absolute pressure, in psia, is relative to a vacuum. Differential pressure, in psid, is the difference between two ports. Every pressure channel on the fluids panel is in psig.

Temperature#

NI compares three kinds of temperature sensor:[3]

Sensor

How it works

Range

Trade-offs

Thermocouple

Two different metals, joined at the tip, make a voltage that depends on temperature

About −210 to 1,760 °C

Widest range, but a small, nonlinear signal

RTD

A metal winding, often platinum, whose resistance changes with temperature

About −240 to 650 °C

Best accuracy, stability and linearity

Thermistor

A resistor, typically with a negative temperature coefficient, whose resistance falls as it heats

About −40 to 250 °C

Most sensitive, but narrowest range

A thermocouple needs cold-junction compensation and amplification.[3] Its voltage depends on the difference in temperature between the tip and the point where its wires connect to the DAQ. The DAQ measures the temperature at that connection, and corrects for it.

The dyno’s motor controllers read a temperature sensor in each motor. The control software treats a reading at or below 0 °C as a sensor fault, such as a missing sensor or a broken wire, rather than a real temperature, and trips the stand. Treating an impossible reading as a fault is the same idea as a current loop’s live zero.

Strain, force and torque#

A strain gauge is a resistor that stretches with the surface it’s bonded to. Strain is the change in length divided by the original length.[4]

The change in resistance is tiny, so strain gauges are wired in a Wheatstone bridge: a quarter, half or full bridge, depending on how many of its four arms are active gauges. A bridge needs excitation, a voltage from the DAQ to power it. A shunt calibration checks the bridge’s output by switching in a known resistor.[4]

A load cell measures force with strain gauges in a bridge,[4] and a torque sensor does the same on a twisting shaft. The dyno has no torque sensor. It calculates torque from motor current instead, as shown below.

Flow#

A flow meter measures how much fluid passes per unit time. On the fluids panel, fm_1 reports 0 to 100 L/min. The panel’s float gauge is a rotameter: a float rides up a tapered tube as flow increases, and you read it by eye, so it has no channel.

Instruments#

The dyno has two kinds of instrument:

  • Motor controllers. Each one measures its motor’s current, speed and temperature, and switches the power that drives the motor. The computer sends each one a speed or current command about 16 times a second over a CAN bus, and reads back its measurements.

  • A power supply. One box both sources and sinks power on the 48 V bus. It measures its own voltage and current, takes SCPI commands over USB, and holds its setpoint without being resent.

See Communications for the buses and protocols.

An instrument can also have a front panel of knobs, buttons and a screen for running it by hand. While a computer controls it, an instrument can lock its front panel in remote mode, so the two don’t fight.

LabVIEW calls its programs virtual instruments (VIs) “because their appearance and operation imitate physical instruments, such as oscilloscopes and multimeters”, and calls each program’s user interface its front panel.[5] A LabVIEW front panel is software on a screen, not part of an instrument.

From signal to channel#

Software called a driver talks to the DAQ or the instrument, and turns each reading into a channel: a named value in engineering units, such as p_1 in psig. For a transducer, that means scaling the raw signal, like the 4–20 mA formula above. For an instrument that reports in engineering units, the driver decodes its messages.

Some channels are calculated from others. These are derived channels.

Worked example: the dyno’s torque#

The dyno has no torque sensor, so its software calculates each motor’s torque from its current, using a constant per motor:

Motor

Torque at maximum current

Constant

DUT

27.503 Nm at 35 A

0.786 Nm/A

Left load motor

3.812 Nm at 20 A

0.191 Nm/A

Right load motor

3.800 Nm at 20 A

0.190 Nm/A

A load motor drawing 10 A is producing about 1.9 Nm. That calculation carries two kinds of error:

  • Every error in the current measurement passes straight through to torque.

  • The constant is a property of the motor, and it doesn’t account for friction or losses between the motor and the axle. A torque sensor on the shaft would measure what reaches the axle.

Because torque is current times a constant, each motor’s torque and current channels always move together.

Choosing a sensor#

When you choose a sensor, check:

  • Range. It covers the values you expect, with headroom for overload.

  • Accuracy. It’s good enough once every error is added up. See Measurement quality.

  • Response time. It’s fast enough for how quickly the value changes.

  • Output. It matches an input you have, such as 4–20 mA or a bridge.

  • Environment. Its temperature range, vibration rating and wetted materials suit the stand.

  • Failure behavior. A failure shows up as an obvious fault, like 0 mA on a current loop, not as a believable value.

Further reading#

References#